Three-phase Voltage and Phase-sequence Phase-loss Relay

K8AK

Download and Discover Our Products

  • Greater resistance to inverter noise.
  • Monitor overvoltages, undervoltages, phase sequence, and phase loss for three-phase 3-wire or 4-wire power supplies with just one Unit.
  • Switch setting for 3-phase 3-wire or 3-phase 4-wire power supply.
  • Two SPDT output relays, 5 A at 250 VAC (resistive load). Output overvoltages and undervoltages using separate relays.
  • World-wide power specifications supported by one Unit (switchable).
  • Output status can be monitored using LED indicator.
Rated input
voltage
K8AK-PM1 Three-phase, three-wire Mode: 200, 220, 230 and 240 VAC
Three-phase, four-wire Mode: 115, 127, 133 and 138 VAC
K8AK-PM2 Three-phase, three-wire Mode: 380, 400, 415 and 480 VAC
Three-phase, four-wire Mode: 220, 230, 240 and 277 VAC
Input load K8AK-PM1: Approx. 4.4 VA
K8AK-PM2: Approx. 4.4 VA
Operating value setting range
(OVER, UNDER)
Overvoltage
 -30% to 25% of rated input voltage
Undervoltage
 -30% to 25% of rated input voltage
Note: The rated input voltage can be switched using the DIP switch.
Operating value 100% operation at set value
Reset value 5% of operating value (fixed)
Reset method Automatic reset
Operating time
setting range (T)
Overvoltage/
undervoltage
0.1 to 30 s
Phase sequence 0.1 s±0.05 s
Phase loss 0.1 s max.
Power ON lock time (LOCK) 1 s or 5 s (Switched using DIP switch.)
Indicators Power (PWR): Green, Relay output (RY): Yellow, OVER/UNDER: Red
Output relays Two SPDT relays (NC operation)
Output relay ratings Rated load
 Resistive load
 5 A at 250 VAC
 5 A at 30 VDC
Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations
         3 A at 250 VAC/30 VDC: 100,000 operations
Ambient operating temperature -20 to 60°C (with no condensation or icing)
Storage temperature -25 to 65°C (with no condensation or icing)
Ambient operating humidity 25% to 85% (with no condensation)
Storage humidity 25% to 85% (with no condensation)
Altitude 2,000 m max.
Terminal screw tightening torque 0.49 to 0.59 N·m
Terminal wiring method Recommended wire
 Solid wire: 2.5 mm2
 Twisted wires: AWG16, AWG18
Note: 1. Ferrules with insulating sleeves must be used with twisted wires.
    2. Two wires can be twisted together.
Recommended ferrules
 Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
 Al 1-8RD (for AWG18) manufactured by Phoenix Contact
 Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact
Case color N1.5
Case material PC and ABS, UL 94 V-0
Weight Approx. 150 g
Mounting Mounts to DIN Track.
Dimensions 22.5 × 90 × 100 mm (W×H×D)
Lorem Ipsum has been the industry's standard dummy text ever since 1500s ?

Lorem Ipsum has been the industry's standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type ...

Lorem Ipsum has been the industry's standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type ...

Lorem Ipsum has been the industry's standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type ...

Lorem Ipsum has been the industry's standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type ...

Get in touch

Subscribe for our latest resources